Model EMV3-A. Every figure below is from Emporia's published technical documentation.
Electrical system support
| Supported systems |
Single-phase 2-wire (up to 240 V) · single-split-phase 3-wire (up to 240/480 V LN/LL) · 3-phase 4-wire “Y” with earthed (TN or TT) neutral, up to 240/415 V LN/LL |
| Not supported |
Delta · 3-wire systems without a distributed neutral |
| Maximum per phase |
200 A (~144 kVA at 415 V) |
| Maximum voltage sense |
264 VAC L-N per channel |
| Voltage channels |
3 |
| Frequency |
50 / 60 Hz |
Measurement
| Accuracy |
±2% |
| Current channels |
3 × 200 A mains · up to 16 × 50 A branch |
| Measurement category |
200 A ports: CAT IV · 50 A ports: CAT III |
| Live data interval |
1 second |
Current sensors
|
Main — 200 A |
Branch — 50 A |
| Maximum current |
200 A |
50 A |
| Internal aperture |
22 mm |
10 mm |
| Body size |
51 × 70 × 40 mm |
29 × 48 × 27 mm |
| Output |
0.333 V |
0.333 V |
| Lead |
~1 m (40″), easily shortened |
~1 m (40″), easily shortened |
| Terminal |
5 mm screw plug, ports A/B/C |
3.8 mm screw plug, ports 1–16 |
Monitor, power and network
| Dimensions |
145 × 70 × 28 mm |
| Mounting |
35 mm DIN rail (2 × M3 screws, not supplied) or surface |
| Power consumption |
Under 3 W |
| Wi-Fi |
2.4 GHz, IEEE 802.11 b/g/n — 5 GHz not supported |
| Ethernet |
10/100Base-T, IEEE 802.3, RJ45 — cable not supplied |
Environmental and certification
| Operating temperature |
−40 °C to 50 °C |
| Humidity / altitude |
0–80% RH · up to 3,000 m |
| Location |
Indoor, dry |
| Certifications |
Safety: UL 61010, UL 2808 (E535044) · EMC: FCC, ISED, CE, PSE, UKCA |
| BIS |
Not BIS certified. Not an approved billing instrument under any Indian utility or government scheme — it is a monitoring device and does not replace your utility meter. |
| Warranty |
1 year, handled in Kolkata |
| Subscription |
None. The Emporia app is free permanently. |
Data retention
| 1-second |
About 3 hours (CSV export only) |
| 1-minute |
7 days |
| 15-minute |
1 year |
| Hourly and above |
Long term |
An internet connection is required — data is processed in Emporia's cloud. Outbound ports 80, 123, 443 and 8883 must be open.
Limits worth reading twice
- Delta supplies are not supported.
- 200 A per phase is a hard ceiling — an over-range sensor understates rather than reads high.
- The 22 mm aperture must clear your service conductor including insulation. Measure at survey.
- 5 GHz-only Wi-Fi will not work.
- No internet, no data — there is no local-only mode.
Which model do I need? →